Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM00988
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/25/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/04/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a grounding detail for the racking and module grounding that shows compliance with NEC art 690.40. 2. Provide a detail showing the inverter and associated equipment mounting. If pole mounted, include distances above grade. If the inverter is mounted at a not readily accessible location, provide compliance with NEC 705.70. 3. Verify that the bus in the service equipment at the exact point of interconnection is factory marked "TAP". If not, provide a letter or document from the manufacturer of the service equipment stating that the line side tap as proposed will in no way compromise the listing or the performance of the equipment, signed by a person that has the authority by that manufacturer to make such a statement. Include all hardware used with a detail. Otherwise, provide for a field evaluation by an NRTL or qualified agency to be performed after the proposed tap is complete to re-certify and maintain the listing of the equipment. NEC 110.3, 230.66. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements. |
| 03/04/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/05/2020 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 03/09/2020 | PMARTIN1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/09/2020 | PMARTIN1 | OUT TO CUSTOMER | Completed |