Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM00970
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide more detail as to how the supply side tap is to be performed… Will it compromise the performance or listing of the service equipment? Verify this with a letter from the manufacturer of the equipment with a statement that the tap performed will in no way compromise the performance or listing of the equipment. The letter must be signed by an agent of that manufacturer who is authorized to do so… Or provide for a NRTL or other authorized Agency to perform a field evaluation of the PV Tap and re- certify the listing of the equipment after the Tap if performed. NEC 110.3. 2. Provide a complete grounding detail for the rack and module bonding. NEC 690.43 A, B. C. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/24/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |