Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM00963
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/27/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Could not locate a response to the electrical comments as requested. 2. Previous comment #2 was not addressed, Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, |
| 09/03/2020 | JPEELDA1 | FIRE | REVIEW | Reqs Change | IFC 2018, 1204.3.3 Smoke Ventilation. The solar installation shall be designed to meet the following requirements: 1. Where non gravity-operated smoke and heat vents occur, a pthway noy less than 4 feet wide shall be provided bordering all sides. 2> Smoke ventillation options, between array sections shall be one of the following: 2.1 A pathway not less than 8 feet wide 2.2 Where gravity-operated dropout smoke and heat vents occur, a pathway not less than 4 feet wide on not fewer than one side 2.3 A pathway not les than 4 feet wide bordering 4-foot by 8-foot venting cutouts every 20 feet on alternating sides of the path-way |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/10/2020 | VLEON1 | APPROVAL SHELF | Completed |
| 09/10/2020 | VLEON1 | OUT TO CUSTOMER | Completed |
| 09/10/2020 | VLEON1 | REJECT SHELF | Completed |