Permit Number: T20CM00963
Parcel: 127090130

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM00963
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2020 MARTIN BROWN FIRE REVIEW Reqs Change Cover sheet states "Not to be used for construction". Please remove this note.
Please add dimensions to plan in order to confirm 4' pathways required by 2018 International Fire Code.
03/09/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change Plans submitted are stamped - Not For Construction - . Submit construction plan set . IBC 107.2.1.

Respond to plan review comments in writting.
03/16/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan recommends. Also provide a written response.
1. Plans submitted are stamped, "Not For Construction". Submit construction plan set . IBC 107.2
2. Provide more detail as to how the supply side tap is to be performed. Include hardware and electrical components utilized.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2020 VLEON1 APPROVAL SHELF Completed
09/10/2020 VLEON1 OUT TO CUSTOMER Completed
09/10/2020 VLEON1 REJECT SHELF Completed