Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM00963
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/25/2020 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Cover sheet states "Not to be used for construction". Please remove this note. Please add dimensions to plan in order to confirm 4' pathways required by 2018 International Fire Code. |
| 03/09/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Plans submitted are stamped - Not For Construction - . Submit construction plan set . IBC 107.2.1. Respond to plan review comments in writting. |
| 03/16/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan recommends. Also provide a written response. 1. Plans submitted are stamped, "Not For Construction". Submit construction plan set . IBC 107.2 2. Provide more detail as to how the supply side tap is to be performed. Include hardware and electrical components utilized. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/10/2020 | VLEON1 | APPROVAL SHELF | Completed |
| 09/10/2020 | VLEON1 | OUT TO CUSTOMER | Completed |
| 09/10/2020 | VLEON1 | REJECT SHELF | Completed |