Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM00932
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/25/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/27/2020 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T20CM00932 - (Religious Use) Parking Lot Solar Canopies (1st Review) 7777 E. Speedway Boulevard - RX-1 Zoning TRANSMITTAL DATE: February 27, 2020 DUE DATE: March 12, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: - Per UDC Article 6.6.3.B Specifically Within Residential Zones, Detached accessory buildings are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line, except for terraces and steps not over three feet high above the natural grade, paved areas, and fences or walls. A Board of Adjustment for Variance will need to be approved prior to approval of the development package. 02. COMMENT: Revise the site plan to match what has been submitted in the Development Package. Once the DP is approved and the building plan documents are consistent with the DP zoning can approve the solar canopy application. 03. COMMENT: Zoning will review the building plans on the next submittal and compare the plans to the approved DP for consistency. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 03/09/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/12/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan recommends. Also provide a written response. 1. Ref; East Service. Line diagrams. Per NEC 230.95, the Main breaker in the existing service equipment is required to be equipped with Ground Fault detection for the protection of the electrical equipment. This is not addressed or shown in the line diagrams. Please verify. If there is Ground Fault Protection, then the PV Interconnection cannot be at the load side of the service equipment unless it meets the requirements of NEC 705.32. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/25/2020 | PMARTIN1 | OUT TO CUSTOMER | Completed |