Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM00919
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan recommends. Also provide a written response. 1. To achieve clarity for review purposes, please revise the numerical order of the electrical plans with a number and letter for each individual plan. There are different buildings and diagrams with the same plan sheet number. 2. Ref; Plan Sheet E-601. Provide information for the 300 amp feeder (Building #4) in the feeder schedule. 3. Additional comments may be generated at the subsequent review due to the arrangement of the plan set if not in some kind of order. 4. Indicate the correct address of the project on the plans. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/29/2020 | LBOWERS1 | OUT TO CUSTOMER | Completed |
| 04/29/2020 | LBOWERS1 | REJECT SHELF | Completed |