Permit Number: T20CM00887
Parcel: 130181390

Address:
3957 E 32ND ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM

Permit Number - T20CM00887
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2020 TOM WEIDEMAN ZONING REVIEW Completed
02/07/2020 TWEIDEM1 BUILDING-RESIDENTIAL REVIEW Reqs Change THE ENGINEERING STAMPS SHOWN ON THE SUBMITTED PLANS, PE CALCULATIONS AND PE LETTER REQUIRE A SIGNATURE AND A DATE SIGNED.

THE COT HAS ADOPTED 115 MPH WIND SPEEDS. UPDATE THE PE CALCS. AND LETTER ACCORDINGLY.

CLARIFY ON THE PLANS IF AN UPGRADED MAIN PANEL WILL BE A PART OF THIS PERMIT. IF SO, REMOVE THE NOMENCLATURE FROM THE ONE LINE AND THREE LINE DIAGRAMS OF THE PLANS.

SUBMIT CORRECTED PLANS, AND ENGINEERING DOCUMENTS PER OUR FILENAMING GUIDELINES, I.E., 2_ PLANS, 2_STAMPED PE CALCS...

SINCERELY,

Tom Weideman
Permit Technician
City of Tucson
520-837-6823
02/07/2020 TOM WEIDEMAN ENGINEERING REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2020 TWEIDEM1 APPROVAL SHELF Completed
02/07/2020 TWEIDEM1 OUT TO CUSTOMER Completed
02/07/2020 TWEIDEM1 REJECT SHELF Completed