Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM00880
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a note on the power plan for compliance with NEC 517.13 for wiring methods of the branch circuits. 2. Provide for Tamper Resistant Receptacles as required per NEC 406.12 (5). Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 02/07/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 02/07/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the number of ice machines being installed. Two are scheduled but only one is shown on the plumbing plan. |
| 02/07/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/12/2020 | LSHAMIS1 | ZONING | REVIEW | Approved | |
| 02/12/2020 | LSHAMIS1 | ENGINEERING | REVIEW | Passed | |
| 02/12/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/13/2020 | PMARTIN1 | OUT TO CUSTOMER | Completed |