Permit Number: T20CM00880
Parcel: 12113649C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00880
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a note on the power plan for compliance with NEC 517.13 for wiring methods of the branch circuits.
2. Provide for Tamper Resistant Receptacles as required per NEC 406.12 (5).
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
02/07/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/07/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify the number of ice machines being installed. Two are scheduled but only one is shown on the plumbing plan.
02/07/2020 ROBERT SHERRY WATER REVIEW Completed
02/12/2020 LSHAMIS1 ZONING REVIEW Approved
02/12/2020 LSHAMIS1 ENGINEERING REVIEW Passed
02/12/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2020 PMARTIN1 OUT TO CUSTOMER Completed