| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2020 | NICHOLAS ROSS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: Nick Ross Lead Planner PROJECT: T20CM00843 & T20CM00847 63 E. 13th Street New Fence and Two Roof Replacements TRANSMITTAL: 4/21/20 COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8). This site is located in the HC-3 zone (UDC 4.7.22). The applicant is proposing to add fencing to the property and to replace the roof on each structure on site. Historic review is required. |
| 04/22/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/22/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Correct the plumbing fixture schedule. The minimum trap size for a kitchen sink shower, clothes washer, or a dishwasher is 1-1/2" . A refrigerator wall box and a hose bibb do not have waste lines. (see Table 709.1, IPC 2018).[Initial comment: Correct the size of the fixture drain from the kitchen sink in unit 33.] 2. Coordinate the plumbing waste isometric with the second level plumbing plan. The clothes washer fixture drain appears to connect to the lavatory fixture drain on the isometric. (The clothes washer is also labeled as P-6.) [Initial comment: The fixture drain from a clothes washer must connect to a horizontal drain that is at least 3" in size. In unit 35, the clothes washer fixture drain and the lavatory fixture drain connect to form a 2" horizontal drain.] 3. Coordinate the plumbing fixture marks in the plumbing fixture schedule with the mark shown inthe plumbing plans. Delete the fixtures that are not used (e.g. P-5). |
| 04/22/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Make up air for a dryer does not require an exhaust fan.; it requires a source of transfer air. See Section 504, IMC 2018 for the requirements. [Initial comment: Provide make up air for the clothes dryers. See Section 504, IMC 2018.] |
| 04/24/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |