Permit Number - T20CM00847
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/07/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/07/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide AFCI and GFI protection as required per 2017 NEC 210.8(A) and (D), 210.12(A). 2. Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code 3. Provide compliance with the 2018 IECC for lighting. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
02/11/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating/cooling load calculations that justify the new a/c units. 2. The IRC is not the controlling code. Provide calculations for the mandatory mechanical ventilation for each dwelling unit. See Section 403, IMC 2018. 3. Provide make up air for the clothes dryers. See Section 504, IMC 2018. 4. |
02/11/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The 2018 IPC is the controlling code. 2. Provide water pressure calculations to verify the sizing of the water distribution system. Note that PEX piping requires the use of the manufacturer's sizing tables. 3. Correct the size of the fixture drain from the kitchen sink in unit 33. 4. The fixture drain from a clothes washer must connect to a horizontal drain that is at least 3" in size. In unit 35, the clothes washer fixture drain and the lavatory fixture drain connect to form a 2" horizontal drain. |
02/11/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. A single 5/8" water meter serves the single-family residence and the triplex. Provide water demand calculations to show what size water meter will be required to serve these two buildings or if an additional water meter (or meters) will be installed. 2. The water pressure available to the site is 42 PSI. Provide calculations to show that this will be adequate for the second-floor residence. 3. Contact Tucson Water - New Services if changes will be made to the water service to the two buildings. |
02/27/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: T20CM00847 69 E 13TH Street Remodel Triplex TRANSMITTAL: February 5, 2020 COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8). This site is located in the HC-3 zone (UDC 4.7.22). Historic review due to exterior placement of mechanical equipment. |