Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM00821
Parcel: 11515110B

Address:
525 W PLATA ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM00821
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2020 JPEELDA1 FIRE REVIEW Approved
07/29/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide storm drainage for the north half of the addition. Reference: Section 1101.7, IPC 2018
07/29/2020 ROBERT SHERRY WATER REVIEW Completed
07/29/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/13/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G1.0; Code Analysis Data (General Building Summary): The Allowable Building Area references the IBC Table 503. Please revise that to the 2018 IBC table reference.
2. Sheet G1.0; Code Analysis Data (Summary of Governing Regulations): The Electrical Code references the 2012 NEC. Please revise that reference.
3. Sheet G1.0; Code Analysis Data: Please indicate on this sheet calculations for the required plumbing fixtures (including the new building occupants). Verify the requirements of the IBC Section 2902.3.3 are met.
4. Sheet S2.3; Roof Framing Plan: At several locations on this plan, framing is called out as TTI. That mark does not show up in the schedule. Please provide.
5. Sheet A1.0; Wall Legend: The masonry walls depicted in the Wall Legend are not indicated on the Floor Plan. Please provide.
6. Sheet A1.0; Floor Plan: The existing wall on the west side of the new building indicates a 2 hour fire rated wall assembly. Please verify this is a fire wall meeting all requirements of the IBC Section 706, and the existing doors in that wall meet the requirements of the IBC Table 716.1(2). Indicate this information on the Floor Plan.
7. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
8. General: Please provide written responses to all review comments.
08/20/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. There was no plan review response to the previous electrical plan review comments located in this plan submittal, as requested. 2.
2. The IECC Comcheck submitted for lighting does not correlate with the IECC lighting calcs on plan sheet E-1.
3. The line diagram on plan sheet E-1 shows 2 panel 'M's, please clarify.
4. Show the location of the electrical service on the power plan.
5. Provide a complete luminaire schedule include lamp color temperature output. Correlate with the Outdoor Lighting lumen calculations.
6. Provide a complete grounding detail for the electrical service that complies with NEC art 250 for all grounding and bonding.
7. Provide the electrical service size in amps, phase, on the line diagram.
8. Provide conduit, conductor sizes and types for the panel feeders.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2020 JGARCIA1 APPROVAL SHELF Completed
08/27/2020 JGARCIA1 OUT TO CUSTOMER Completed
08/27/2020 JGARCIA1 REJECT SHELF Completed