Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM00821
Parcel: 11515110B

Address:
525 W PLATA ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00821
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan recommends. Also provide a written response.
1. The submitted line diagram for the electrical services (1 sheet not assigned a number) is significantly different from the original. For example; the original approved plan (line diagram) shows Building 'A' service feeding AC units, this revised Line Diagram shows the service feeding suites in the building addressed as 525 W Plata. Please submit complete lighting and power and electrical site plans that correlate with the revised plan. Show the locations of all electrical equipment, such as panels, etc.
2. The revised Line Diagram plan is missing the following;
(a) Voltage and Phase.
(b) Grounding detail.
(c) Amp Rating.
(d) AIC Ratings of the service and downstream electrical equipment.
(e) Fuse types in the disconnect switches.
(f) Feeder conduit and conductor sizes and types and destinations or terminations at equipment in the suites.
(g) Explain how the secondary feeders are terminating in the 12x12 Gutters. And how the feeders to the Meters are terminated in the gutters.
(h) Assign the building letters to the corresponding addresses.
(i) Identify what is new and what is existing for equipment or feeders.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.