Permit Number: T20CM00809
Parcel: 11619377B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00809
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2020 MARTIN BROWN FIRE REVIEW Approved
03/10/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change Reviewer: Chris Anderson, March 4, 2020
BUILDING - COMMERCIAL
1. Please respond to all review comments in writing, citing Code references to justify designer's position where disagreement occurs with the review comment.
2. The demolition plan, sheet DA101, shows a 12'-0" wide x 14'-0" high cutout being made in the precast concrete exterior wall. While detail 4, sheet A001, shows steel reinforcing around this opening you must submit structural calculations sealed by an Arizona registrant for this work. Ref. 2018 IBC 107.2.1.
3. The plan key on sheet A001 shows a wall hatch for "new 2-hour firewall" and "existing 2-hour firewall." There seems to be hatching for a new firewall only in the General Archive adjacent to the Entry Passage. Please explain what this is. Ref. 2018 IBC 107.2.1.
4. On the Floor Plan, sheet A101, Type A partition is shown in various locations for the walls enclosing the Object Repository space. It is the Architect's intent that this type A designation is for the entire perimeter of this room or just for the locations bearing the "A" marker? If for the entire perimeter please clarify on the plan. Ref. 2018 IBC 107.2.1.
5. Please show the surface mounted steel opening reinforcing for the sawcut doorway on detail 2/A101 in accordance with detail 4/A001 to show how overhead door mechanism and cowling will fit. See also, building review comment 2. Ref. 2018 IBC 107.2.1.
03/10/2020 PIMA COUNTY WATER REVIEW Passed
03/10/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Passed
03/10/2020 LOREN MAKUS ENGINEERING REVIEW Passed
03/10/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
03/10/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2020 LBOWERS1 REJECT SHELF Completed