Permit Review Detail
Review Status: Active
Review Details: RESUBMITTAL
Permit Number - T20CM00808
Review Name: RESUBMITTAL
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/06/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/06/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/06/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Povide structural calculations and details for the location of the gas-fired water heater into the attic. 2. Show maintenance access for the water heater 3. Show how the water heater will be vented 4. Clarify the revisions to the water distribution system |
02/06/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/06/2020 | ANY | REJECT SHELF | RECEIVED |