Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM00767
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/03/2020 | DJELLEN1 | ZONING | REVIEW | Approved | |
02/03/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the ventilation calculations using "Nail Salon" instead of "beauty salon". 2. Recirculation of the air supplying a nail salon shall not be recirculated to other occupancies. Reference: Footnote b, Table 403.3.1.1, IMC 2018. |
02/03/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/03/2020 | DJELLEN1 | ENGINEERING | REVIEW | Passed | |
02/03/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. lease adjust the occupat loads to reflect the number of chairs on the temant space. 2. The point of use water station is required to be plumbed with a water supply. Locate along an accessible route. |
02/03/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/03/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide point of use water supply in lieu of a drinking funtain. |
02/03/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/03/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/07/2020 | JWILLIA2 | REJECT SHELF | Completed |