Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM00715
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/30/2020 | NMARTEL1 | ENGINEERING | REVIEW | Passed | |
01/30/2020 | NMARTEL1 | OIP | REVIEW | Passed | |
01/30/2020 | NMARTEL1 | ZONING | REVIEW | Approved | |
02/05/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Enlarge plan, Minimum text or font is required to be 3/32". 2. Show the location of the 200 amp pedestal on the site plan. 3. Revise the NEC to the current 2017. 4. Indicate the AIC rating of the electrical service equipment per TEP. 5. Indicate the size and type of the Grounding Electrode Conductor. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements. |
02/05/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
02/05/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/05/2020 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/11/2020 | PMARTIN1 | OUT TO CUSTOMER | Completed |