Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM00708
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/05/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 03/05/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | Approval of DP20-0031 is required prior to approval of the building plans |
| 03/05/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/05/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Electrical Site Plan. (a) Indicate branch circuit(s) number, rating of OCPD(s), and panel. (b) Revise the Code reference to the current 2017 NEC not 2018. (c) Indicate conduit sizes and types on the plan. (d) Indicate the correct code section at the gate. No section 438 in the NEC Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements. |
| 05/08/2020 | ARUIZ1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/08/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |