Permit Number: T20CM00701
Parcel: 107091090

Address:
2640 N 15TH AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T20CM00701
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2020 ANDREW CONNOR NPPO REVIEW Passed
08/31/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Roof projections may not extend to a point closer than 2 feet from the property line. Provide notation for compliance with R302.1 (City of Tucson Amended) by removing the roof overhang near the property line, or provide a complete wall barrier with not less than one-hour fire-resistive construction above the roof line.
09/01/2020 JOHN VAN WINKLE ENGINEERING REVIEW Passed
09/04/2020 MALLORY RESS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Mallory Ress
Planner

PROJECT:
T20CM00701
2640 N 15TH AV
CARPORT ADDITION

TRANSMITTAL: Date 9/4/20
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).

The applicant is proposing a 2-foot setback to the north property line. With a wall height of 8’6" to natural grade, a 6-foot setback is required.

The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a).

The DDO process may only be used to reduce the driveway length to a carport, and not to a garage (UDC Section 3.11.1.B.4).

The applicant is proposing a front facing attached carport with a wall height of 11’1" to natural grade facing the street perimeter (west) lot line. An 8’ setback is proposed to the west lot line and a 20’ setback is required.

DDO is required.

Note, see Residential review comments as proposed fire rating is required. Plans may change and DDO comments may need to be updated.