Permit Number: T20CM00651
Parcel: 11103077A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM00651
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The re-submitted plans aren't sealed.
2. The electrical review comment was not addressed. Could not locate the racking and module grounding detail on plan sheet E-3 as stated in the response letter.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.