Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM00618
Parcel: 117033180

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T20CM00618
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Since the Type II hood has been deleted from the activity, remove it from drawings P1 and M1. Reference: Section 107.2.1, IBC 2018.
2. Clarify the location of the discharge from EF-1 with regard to walkways and the distance requirements of Section 501.3.1 (3), IMC 2018.
3. The removal of the type II hood over the existing convection oven and the new 4-deck convection oven will result in an addition to the cooling load in the space (the 4-inch exhaust duct on the new hood is for steam removal only). Verify that the proposed heat pump (FC-1/CU-1) can handle the added load. Reference: Section 507.3, IMC 2018
04/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that ready access to the floor sink, P-1 is not blocked by the proposed 4-deck oven. Reference: Section 802.4, IPC 2018.
05/05/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/17/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/18/2021 NGARCIA3 OUT TO CUSTOMER Completed