Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T20CM00618
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/27/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Since the Type II hood has been deleted from the activity, remove it from drawings P1 and M1. Reference: Section 107.2.1, IBC 2018. 2. Clarify the location of the discharge from EF-1 with regard to walkways and the distance requirements of Section 501.3.1 (3), IMC 2018. 3. The removal of the type II hood over the existing convection oven and the new 4-deck convection oven will result in an addition to the cooling load in the space (the 4-inch exhaust duct on the new hood is for steam removal only). Verify that the proposed heat pump (FC-1/CU-1) can handle the added load. Reference: Section 507.3, IMC 2018 |
04/27/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that ready access to the floor sink, P-1 is not blocked by the proposed 4-deck oven. Reference: Section 802.4, IPC 2018. |
05/05/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/17/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/18/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |