Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM00618
Parcel: 117033180

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM00618
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The revised water heater weighs more than 500-pounds. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Coordinate the detail on sheet S4 with the with the detail on sheet P2. Reference: Section 301.2, IPC 2018.
05/22/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Update the COMcheck mechanical compliance certificate to include the additional efficiency package (high efficiency HVAC) and show the revised storage-type water heater (from 20-gallons to 50-gallons). [Initial comment: Show how one of the "Additional Efficiency Package Options" (C406, IECC 2018) is to be accomplished. Reference: Section C401.2, IECC 2018.]
2. Comment not addressed. [Initial comment: Show that the walk-in cooler and the walk-in freezer meet construction and performance requirements of Sections C403.10.2 and C403.10.2.1, IECC 2018.]
05/26/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/26/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/03/2020 ARUIZ1 ZONING REVIEW Needs Review