Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T20CM00618
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/22/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The revised water heater weighs more than 500-pounds. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Coordinate the detail on sheet S4 with the with the detail on sheet P2. Reference: Section 301.2, IPC 2018. |
05/22/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Update the COMcheck mechanical compliance certificate to include the additional efficiency package (high efficiency HVAC) and show the revised storage-type water heater (from 20-gallons to 50-gallons). [Initial comment: Show how one of the "Additional Efficiency Package Options" (C406, IECC 2018) is to be accomplished. Reference: Section C401.2, IECC 2018.] 2. Comment not addressed. [Initial comment: Show that the walk-in cooler and the walk-in freezer meet construction and performance requirements of Sections C403.10.2 and C403.10.2.1, IECC 2018.] |
05/26/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/26/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/03/2020 | ARUIZ1 | ZONING | REVIEW | Needs Review |