Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM00605
Parcel: 127100930

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM00605
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2020 ROBERT SHERRY WATER REVIEW Completed
05/14/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: State the sequence of operation for the exhaust fans EF10 and EF11. Reference: Section 403.2.1 (4), IMC 2018.]
05/14/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. [Initial comment: Provide specifications for the two new restroom lavatories and faucets. Reference: Sections 303.4 and 402, IPC 2018, Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]
2. Comment not addressed. [Initial comment: Provide the hot water demand that is to be served by water heaters, WH1 and WH2. Show how the two water heaters will be able to fulfill the hot water demand with a minimum water temperature of 110 degrees Fahrenheit (approximately a minimum 80-degree rise). Reference: Section 607.1, IPC 2018.]
3. Comment not addressed. [Initial comment: Interior waste piping upstream of the grease interceptor shall have a minimum slope of ΒΌ" per foot (2% slope). Reference: Section 704.1, IPC 2018.]
05/20/2020 ARUIZ1 BUILDING-COMMERCIAL REVIEW Needs Review
05/20/2020 ARUIZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review