Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM00605
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/14/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Initial comment: State the sequence of operation for the exhaust fans EF10 and EF11. Reference: Section 403.2.1 (4), IMC 2018.] |
| 05/14/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. [Initial comment: Provide specifications for the two new restroom lavatories and faucets. Reference: Sections 303.4 and 402, IPC 2018, Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.] 2. Comment not addressed. [Initial comment: Provide the hot water demand that is to be served by water heaters, WH1 and WH2. Show how the two water heaters will be able to fulfill the hot water demand with a minimum water temperature of 110 degrees Fahrenheit (approximately a minimum 80-degree rise). Reference: Section 607.1, IPC 2018.] 3. Comment not addressed. [Initial comment: Interior waste piping upstream of the grease interceptor shall have a minimum slope of ΒΌ" per foot (2% slope). Reference: Section 704.1, IPC 2018.] |
| 05/20/2020 | ARUIZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 05/20/2020 | ARUIZ1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |