Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM00596
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The vent protecting the grease interceptor from pressure fluctuations is to be connected downstream of the grease interceptor. Reference: Sections 901.2 and 1003.9, IPC 2018. [Initial comment: Show the connection of the vent for the gravity grease interceptor to the existing vent (keynote 8).] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2020 | SBORZAK1 | OUT TO CUSTOMER | Completed |