Permit Number: T20CM00537
Parcel: 134220430

Address:
6702 E COOPER ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T20CM00537
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2020 NMARTEL1 NPPO REVIEW Passed
01/23/2020 NMARTEL1 ENGINEERING REVIEW Passed
03/10/2020 NMARTEL1 ZONING REVIEW Approved ZONING REVIEW TRANSMITTAL

FROM: Nicholas Martell
Planner

PROJECT:
T20CM00537
6702 E Cooper St.
Master Suite Addition

TRANSMITTAL: 1/23/2020
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b).

The applicant is proposing a 6' setback based on a wall height of 8'-11 ¼". The required setback is 10'.

DDO is required.
03/10/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed