Permit Number: T20CM00522
Parcel: 117101010

Address:
250 N MEYER AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T20CM00522
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the revision narrative with the revised mechanical plans. The narrative calls for a 3.5-ton AC unit to be refurbished in lieu of installing a new 5-ton AC unit but no 3.5-ton AC unit is shown on the mechanical drawings.
06/15/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/17/2020 ARUIZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2020 ARUIZ1 APPROVAL SHELF Completed