Permit Number: T20CM00522
Parcel: 117101010

Address:
250 N MEYER AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00522
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2020 JVINCEN1 FIRE REVIEW Approved
02/19/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Completed
02/19/2020 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Completed 1. Specify how the bathroom exhaust fans will exhaust all of the air required to be exhausted to the outdoors. Specify operational sequence for operation for the exhaust fans when the bathroom is not occupied. ICM 501.4
02/19/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. TS1 Where the occupant load exceeds 15 persons, not less two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. IBC TABLE 2901.1.
2. TS1 Per IBC Table 2901.1 a service sink is required for business classifications with an occupant load exceeding 15 persons.
3. A2.0 Where counters are provided for sales or distribution of goods or services a portion of the counter surface shall be not more than 36" in height. IBC 1109.12.3, ICC A117.1 Section 904.
4. A1.0 Provide construction details of the fastening and bracing of new walls at the roof/ceiling. Specify fasteners and bracing methods. IBC 1607.15.
5. A1.0 Identify and label all EXITS from the tenant improvement space. IBC 1028.1.
6. A2.0 Provide material and installation details of the new metal suspension system for new acoustic lay-in tile system. IBC 808.1.
02/19/2020 RMCCOY1 WATER REVIEW Passed
02/19/2020 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Reqs Change 1. TS1 Per IPC TABLE 403.1, a service sink is required for business classifications with an occupant load exceeding 15 persons.
2. TS1 Where the occupant load exceeds 15 persons, not less two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. IPC 410.