Permit Number: T20CM00489
Parcel: 13014009D

Address:
4380 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00489
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2020 LSHAMIS1 ZONING REVIEW Approved
03/13/2020 LOREN MAKUS ENGINEERING REVIEW Passed
03/16/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan recommends. Also provide a written response.
1. Assign branch circuits for the replaced or new power and lighting, include mechanical equipment and Correlate with the panel schedule.
2. Provide a complete panel schedule, include revised load calcs.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
03/16/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/16/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/16/2020 MARTIN BROWN FIRE REVIEW Approved
03/16/2020 ROBERT SHERRY WATER REVIEW Completed
03/17/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1.0 (Sheet Index); Sheet A1.0 (Title): The Sheet Index on Sheet T1.0 and the Title on Sheet A1.0 indicate "Partition Detail". Please revise that to Partition Types.
2. Sheet T1.0 (Sheet Index); Sheet A2.0 (Title): The Sheet Index on Sheet T1.0 and the Title on Sheet A2.0 indicate "Restroom Specifications + Interior Elevations". Please revise those descriptions since there are no specifications or elevations on that sheet.
3. Sheet A1.0; Partition Types: Two Partition Types have the same W2 callout. Please revise.
4. Sheets A1.0, A2.0, A3.1, and A4.0: The architectural seal indicates "Preliminary Not For Construction". Please remove that note and sign/date the seal.
5. General: Please provide written responses to all review comments.
03/17/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed