Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM00486
Parcel: 11720016G

Address:
108 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00486
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2020 MROSS2 FIRE REVIEW Approved
02/18/2020 IMONSHI1 ZONING REVIEW Reqs Change Exterior elevations dont match that of the ones shown on the approved historic plan. Contact Micheal Taku
02/26/2020 ROBERT SHERRY WATER REVIEW Completed
02/27/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
02/27/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL - COMMERCIAL
1. Submit heating and cooling load calculations to justify the capacities of selected equipment.
2. Submit mechanical COMcheck.
02/27/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change Reviewer: Chris Anderson, February 14, 2020
BUILDING - COMMERCIAL
1. Please respond to all review comments in writing, citing Code references to justify designer's position where disagreement occurs with the review comment.
2. There appears to be no formal agreement at this time with the Pima County/ City of Tucson Historic Plans Review Committee regarding the work regarding the façade of this existing structure. Please submit an approval letter that would allow you to proceed with the proposed façade work.
3. On sheet G-02 the imaginary line between buildings on this same lot is shown 3'-0" from the existing structure being reviewed on the east and south sides. The existing adobe wall is labeled "(E) 1-hour fire-rated adobe wall" and there are existing window and door openings. Please provide justification for the existing adobe walls being 1-hour fire-rated.
4. On sheet G-02 under "gross floor area" it is noted that the 2nd floor has an area of 1000 SF. While there is no work planned for this floor, this entire building on the ground floor and exterior is being rehabilitated, including an addition and new bathrooms. Please show in these documents what the 2nd floor area will be used for and show that only a single exit is required for this 1000 SF space.
5. Per 2018 IECC On sheet A-04, exterior walls of the new addition are not prescriptively insulated in accordance with the 2018 IECC Table C402.1.3. Either provide continuous R-5.7 insulation or a building envelope COMcheck showing compliance with the energy code.
6. Either in the specifications, sheet G-03 or the door and window schedules, sheet A-12, specify the U-values and SHGC required by the 2018 IECC Tables C402.1.2 and C402.3 for new doors, windows and storefront in exterior walls.
7. On sheet A-13, the accessible toilet compartments shall match what is allowed by Fig. 604.9.3.1(a) or (c) of the ICC/ANSI A117.1-2009. Either move the compartment door to 4" from the sidewall and relocate the toilet to the opposite side wall per configuration (a) or extend the compartment wall and swing the door into the compartment per configuration (c).
8. On toilet room elevations 4, 12, 18 and 23, sheet A-14, show the vertical grab bar at toilet sidewalls per ICC/ANSI A117.1-2009 Fig. 609.5.1.
9. On ramp elevation/section 13, sheet A-15, the handrail extension at the bottom of the stair run shall extend the same width of the stair tread from the bottom step nosing per ICC/ANSI A117.1-2009 Fig. 505.10.1. Please indicate this on the drawing.
10. Detail 6/A-18 (wall type F) show a new exterior wall attached at the base to a concrete slab. As shown the weep screed does not comply 2018 IBC 2512.1.2 requiring weep screeds to be located at or below the foundation plate line and minimum 2" above paving. Add a minimum 2" high concrete or masonry curb to accommodate this Code section.
02/27/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2020 ARUIZ1 OUT TO CUSTOMER Completed