Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM00481
Parcel: 137051000

Address:
5065 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00481
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2020 MROSS2 FIRE REVIEW Approved
02/07/2020 LSHAMIS1 ZONING REVIEW Needs Review FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T20CM00481
Commercial Tenant Improvement (1st Review)
5056 S 12th Ave

TRANSMITTAL DATE: February 6, 2020

DUE DATE: February 25, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: The proposed use for this site is Commercial Service Use - Restaurant, which is a change from existing use Retail. This will require a development package and UDC compliance with the correct purposed use.


If you have any questions about this transmittal, Contact Loran Shamis by email Loran.Shamis@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
02/19/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Code Review: Per the IBC Table 2902.1, please indicate on this sheet the required number of drinking fountains and service sinks, and the number provided.
2. Sheet A1; Code Review: Item #7 indicates 1 per 75 water closets are required. Per the IBC Table 2902.1 (Mercantile), the water closets required are one fixture per 500 occupants for each sex. Please revise this sheet.
3. Sheet A1; Code Review: Item #7 indicates 1 per 200 lavatories are required. Per the IBC Table 2902.1 (Mercantile), the lavatories required are one fixture per750 occupants for each sex. Please revise this sheet.
4. Sheet A1; Code Review: Please include on this sheet the allowable building area (per Table 506.2), the allowable building height in stories (per Table 504.4), and the allowable building height in feet (per Table 504.3).
5. Sheet A1; Code Review: Please include on this sheet the number of required exits (per Table 1006.3.2), and the total means of egress capacity (in inches) per Section 1005.
6. Sheet A1; Site Plan: Please provide a site plan in this set of drawings that provides the information listed in the IBC Section 107.2.6.
7. Sheet A3; Interior Partition Detail 1: Please add diagonal bracing at the top of the interior partition to resist horizontal loading as required by the IBC Section 1607.15. Indicate bracing size and spacing, and the number and size of connectors to the top of the partition and to the roof structure above. An alternate would be to run the partition studs to the roof deck above for the connection.
8. Sheet A3; Water Heater Detail 2: The exterior wall is masonry, but this detail indicates metal studs. Please revise and indicate a connection of the ledger to the masonry wall.
9. Sheet A3; Plan Notes: The last plan note references accessible seating per the IBC Section 1108.2.9.1. On this sheet, please indicate the total number of seats, the required number of accessible seats (per Section 1108.2.9.1), and the actual number of accessible seats. Show those seats on the plan.
10. Sheet A6; Key Notes: Notes 2, 9, and 11 are not located on the water closet wall elevations. Please verify.
11. General: Please review the IBC Section 107 for required information/documents, and verify those requirements are provided.
12. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
02/24/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the site plan to show the property lines and the distance of the building walls from the property lines. Reference: Section 107.2.6, IBC 2018.
2. Show how the proposed termination of the Type I exhaust duct and exhaust fan complies with requirements of Sections 506.3.13.2 and 506.3.13.3, IMC 2018.
02/24/2020 ROBERT SHERRY WATER REVIEW Completed
02/24/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise detail 208 to indicate that the distance from the hot water source to the hot water termination for the public lavatories must comply with the requirements of Section C404.5, IECC 2018.
2. The specified water heater has a weight of approximately 990 pounds when full. Detail 206 shows it mounted in an 18"-high platform but the plumbing water floor plan shows it mounted above the mop sink. Clarify how the water heater is mounted and, if it is mounted above the mop sink, provide structural calculations and details for the installation. Reference: Section 307.1, IPC 2018.
3. Provide a cleanout for the horizontal grease waste line running north from the floor sink, P-4, that serves the 3-compartment sink. Reference: Sections 708.1.1 and 708.1.8, IPC 2018.
4. Revise detail 212 to provide an air gap for food-handling fixtures (e.g. prep sinks). The detail calls for an air break. Reference: Sections 801.2, 802.1.1, and 802.3.1, IPC 2018.
02/28/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please revise the 2012 IECC lighting calcs to the current 2018,