Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a complete line diagram. Include grounding, wiring methods, overcurrent protective devices Provide the correct model number and specs of the generator.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.