Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/07/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a complete line diagram. Include grounding, wiring methods, overcurrent protective devices Provide the correct model number and specs of the generator. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
02/07/2020 | LSHAMIS1 | ZONING | REVIEW | Approved | |
02/07/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |