Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T20CM00405
Parcel: 211350170

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM00405
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2020 JVINCEN1 FIRE REVIEW Approved
02/12/2020 IMONSHI1 ZONING REVIEW Reqs Change UNTIL DP20-0011 HAS BEEN APPROVED THE BUILDING PLANS CANNOT BE APPROVED.

-I.M 2/12/2020
02/26/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/26/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet Cover; Building Code Information: Please provide the Occupancy Classification per the IBC Chapter 3, and the Construction Type per the IBC Chapter 6, on this sheet.
2. Sheet SG301; Purlins: Are the purlin designations shown on this sheet indicated on the physical erected purlins for inspector identification? Please verify.
3. Sheet SG302 (Spread Footing Schedule); Structural Calculations (Page 14): The footing reinforcement in the calculations indicates (6) #4 bars (or 5-#5) top and bottom longitudinal and transverse, while the schedule indicates (4) #4 top and bottom (or 4-#5) for reinforcing parallel to the post web, and (6) #4 top and bottom (or 5-#5) for reinforcing perpendicular to the post web. Please coordinate.
4. General: Please provide a Special Inspection Certificate with parts A and B completed. This may be found at www.tucsonaz.gov/PDSD.
5. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
03/02/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change Provide an approved floodplain use permit from Pima County RFCD for this project.

Development Package approval required prior to building permit approval

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2020 VLEON1 APPROVAL SHELF Completed
09/28/2020 VLEON1 OUT TO CUSTOMER Completed
09/28/2020 VLEON1 REJECT SHELF Completed