Permit Number: T20CM00402
Parcel: 211350170

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM00402
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2020 MARTIN BROWN FIRE REVIEW Approved
02/26/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/26/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet Cover; Building Code Information: Please provide the Occupancy Classification per the IBC Chapter 3, and the Construction Type per the IBC Chapter 6, on this sheet.
2. Sheet SG301; Purlins: Are the purlin designations shown on this sheet indicated on the physical erected purlins for inspector identification? Please verify.
3. Sheet SG302 (Spread Footing Schedule); Structural Calculations (Page 14): The footing reinforcement in the calculations indicates (6) #4 bars (or 5-#5) top and bottom longitudinal and transverse, while the schedule indicates (4) #4 top and bottom (or 4-#5) for reinforcing parallel to the post web, and (6) #4 top and bottom (or 5-#5) for reinforcing perpendicular to the post web. Please coordinate.
4. General: Please provide a Special Inspection Certificate with parts A and B completed. This may be found at www.tucsonaz.gov/PDSD.
5. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
03/03/2020 LSHAMIS1 ZONING REVIEW Approved
03/20/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change Provide copy of Pima County Regional Flood Control District Floodplain Use Permit for this project.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2020 VLEON1 APPROVAL SHELF Completed
09/28/2020 VLEON1 OUT TO CUSTOMER Completed
09/28/2020 VLEON1 REJECT SHELF Completed