Review Details: RESUBMITTAL
Permit Number - T20CM00377
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/25/2021 | JGARCIA1 | WATER | REVIEW | Completed | |
| 04/02/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. DP must be approved first. 2. Clearly show how primary roof drains will not be discharged over pedestrian routes. |
| 04/14/2020 | NICHOLAS ROSS | ZONING | REVIEW | Reqs Change | PDSD Zoning Review Section PROJECT: T20CM00377 - PROJECT Building Plan Review (2nd Review) 4030 E 22ND ST / C-2 Zoning TRANSMITTAL DATE: April 14, 2020 DUE DATE: April 14, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Commercial building plans cannot be approved until development package has been approved 2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the Development Package. 3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, Contact Nicholas.Ross@tucsonaz.gov |
| 06/01/2020 | JGARCIA1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Reviewer: Chris Anderson, May 15, 2020 1. PER PREVIOUS BUILDING REVIEW COMMENT 6, “… Drawings, Specifications and COMcheck shall be coordinated and match.” With this submittal drawings and COMcheck match but no revised specifications were submitted to show coordination. Please submit revised Project Manual for confirmation. 2. PER PREVIOUS BUILDING REVIEW COMMENT 7, “Change the U-value for aluminum entrances and storefront in Specification Section 08410 1.3 M from 0.63 to 0.32 to match the COMcheck or revise the COMcheck. Ref. 2018 IBC 107.2.1.” With this submittal no revised specifications were submitted to show coordination. Please submit revised Project Manual. 3. PER PREVIOUS BUILDING REVIEW COMMENT 10, “in the structural calculations, Spread Footing Design Summary, on page 207 of 253, C-1 is shown as 6.5’ x 6.5’; however in the Column Footing Schedule, sheet S2.1, this footing is labeled “F4” and is only 4’ x 4’. Please explain.” No response was made with this submittal. |
| 06/01/2020 | JGARCIA1 | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL 1. PER PREVIOUS MECHANICAL REVIEW COMMENT 2, “please submit heating and cooling load calculations to justify the capacities of equipment specified in the Rooftop Unit Schedule, sheet M3.0. Ref. 2018 IECC C403.3.1.” No heating and cooling load calculations were included in this submittal. |
| 06/01/2020 | JGARCIA1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL – COMMERCIAL 1. PER PREVIOUS ELECTRIC REVIEW COMMENT 1, “submit outdoor lighting lumen calculations per the 2012 Pima County/City of Tucson Outdoor Lighting Code Section 401.2.1 and Table 401.1 for E3 lighting area. The Outdoor Lighting Code can be found on the City of Tucson Planning & Development Services website under the Building Codes link.” No outdoor lumen calculations were provided with this submittal. 2. PER PREVIOUS ELECTRIC REVIEW COMMENT 2, “per the Outdoor Lighting Code 402.1 the maximum color temperature for ALL exterior light fixtures is 3500K. Please confirm that the specified exterior light fixtures do not have a color temperature rating exceeding 3500K.” It appears that some of the outdoor light fixtures are rated at 5000K. No confirmation that none exceed 3500K was provided with this submittal. |
| 06/01/2020 | JGARCIA1 | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING – COMMERCIAL 1. PER PREVIOUS PLUMBING REVIEW COMMENT 1, “please submit the proposed 1000 gallon oil separator to Pima County Regional Wastewater Reclamation Department Industrial Waste Division for review and approval. Contact Steve Valencia at (520) 724-6209 for instructions. Submit IW approval with next submittal.” No memo from PCRWRD IWD was included with this submittal. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/01/2020 | JGARCIA1 | APPROVAL SHELF | Passed |
| 06/01/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
| 06/01/2020 | JGARCIA1 | REJECT SHELF | Completed |