Permit Number: T20CM00377
Parcel: 13014452A

Address:
4030 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM00377
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2020 MARTIN BROWN FIRE REVIEW Approved
02/13/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Please submit the proposed 1000 gallon oil separator to Pima County Regional Wastewater Reclamation Department Industrial Waste Division for review and approval. Contact Steve Valencia at (520) 724-6209 for instructions. Submit IW approval with next submittal.
Provide water calculations to justify domestic water pipe and meter sizes. Ref. 2018 IPC 106.3.1.
02/13/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
Submit outdoor lighting lumen calculations per the 2012 Pima County/City of Tucson Outdoor Lighting Code Section 401.2.1 and Table 401.1 for E3 lighting area. The Outdoor Lighting Code can be found on the City of Tucson Planning & Development Services website under the Building Codes link.
Per the Outdoor Lighting Code 402.1 the maximum color temperature for all exterior light fixtures is 3500K. Please confirm that the specified exterior light fixtures do not have a color temperature rating exceeding 3500K.
Please confirm that the service garage areas are equipped with a gas detection system per 2018 IBC 406.8.2 and that “failure of the gas detection system shall automatically deactivate the heating system, activate the mechanical system where the system is interlocked with the gas detection system, and cause a trouble signal to sound at an approved area.” Ref. 2018 IBC 406.8.2.2.
02/13/2020 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: T20CM00377 - PROJECT
Building Plan Review (1st Review)
4030 E 22ND ST / C-2 Zoning

TRANSMITTAL DATE: February 12th, 2020

DUE DATE: February 25th, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Commercial building plans cannot be approved until development package has been approved

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the Development Package.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
02/13/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING – COMMERCIAL
Reviewer: Chris Anderson, February 7, 2020
Please respond to all review comments in writing. Cite Code references to justify deviations from review comments.
On sheet G1.2 please complete the “Accessibility” section of Building Information. Ref. 2018 IBC 107.2.1.
On sheet G1.2, Means of Egress, use 150 SF per occupant as the 2018 IBC Table 1004.5 load factor to calculate occupancy for Group B – Showroom.
On sheet G1.2, Plumbing Fixtures, change “2012 IPC” to “2018 IPC.”
On the Floor Plan, sheet A2.0, label the door for the file closet 117, “109”. Ref. 2018 IBC 107.2.1.
Please note the insulation R-values on all wall sections, A4 sheets, to match the building envelope COMcheck. Also coordinate the Specifications. For example, the roof insulation shown in detail A4.4 shows R-30 while the Comcheck shows R-25 and Specification 07540 shows R-22. Which is it? Drawings, Specifications and COMcheck shall be coordinated and match.
Change the U-value for aluminum entrances and storefront in Specification Section 08410 1.3 M from 0.63 to 0.32 to match the COMcheck or revise the COMcheck. Ref. 2018 IBC 107.2.1.
There are reviewer’s notes in Sections 07210 and 07540 (and perhaps elsewhere in the Project Manual) that need resolution. Ref. 2018 IBC 107.2.1.
The Geotechnical Report is marked ”DRAFT”. Submit the final report, stamped and signed by the Engineer. Ref. 2018 IBC 107.2.1.
In the structural calculations, Spread Footing Design Summary, on page 207 of 253, C-1 is shown as 6.5’ x 6.5’; however in the Column Footing Schedule, sheet S2.1, this footing is labeled “F4” and is only 4’ x 4’. Please explain.
02/13/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
Outside air requirements are shown in the Rooftop Unit Schedule, sheet M3.0. Please submit calculations to verify amounts shown. Ref. 2018 IMC 403.
Please submit heating and cooling load calculations to justify the capacities of equipment specified in the Rooftop Unit Schedule, sheet M3.0. Ref. 2018 IECC C403.3.1.
Please confirm that the service garage areas are equipped with a gas detection system per 2018 IBC 406.8.2 and that “failure of the gas detection system shall automatically deactivate the heating system, activate the mechanical system where the system is interlocked with the gas detection system, and cause a trouble signal to sound at an approved area.” Ref. 2018 IBC 406.8.2.2.
02/28/2020 AMARTIN1 ENGINEERING REVIEW Reqs Change 1) Approval of DP19-0130 is required prior to approval of the building plans

2) Ensure that roof drains, from the new building, scupper underneath sidewalks as needed. Reference COT Technical Standards Manual (TSM) section 7-01.4.1.e
03/02/2020 PIMA COUNTY WATER REVIEW Reqs Change DUPLICATE FOLDER

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2020 AMARTIN1 OUT TO CUSTOMER Completed
03/19/2020 AMARTIN1 REJECT SHELF Completed