Permit Number: T20CM00339
Parcel: 125140410

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM00339
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Drinking fountain(s) for use by standing persons and persons in a wheelchair shall be provided in the new tenant space. As an alternate, the City of Tucson will accept point of use water dispensers in which: 1. The dispenser is listed and labeled. 2. The dispenser must be connected to a permanent potable water supply. 3. The water supply must be indicated on the plans. 4. The clear floor space of the dispenser is on an accessible route. TABLE 2902.1, City of Tucson policy.
2. Please provide a minimum plumbing fixture analysis per IBC TABLE 2902.1.
Please respond to all comments in writing.