Permit Number: T20CM00313
Parcel: 12513068A

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T20CM00313
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2021 JPEELDA1 FIRE REVIEW Approved
08/27/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/27/2021 ROBERT SHERRY WATER REVIEW Completed
08/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The architectural drawings show a north-south ridge line for the roof deck roughly in the center of the deck. Show how the sole overflow deck drain located at the west edge of the deck will be adequate to drain the entire deck.
Reference: Section 1108.3, IPC 2018
08/27/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Since this was a roof design, and now it is changing to an occupiable deck design, live loads and dead loads will change. Please provide structural calculations, plans, and details as required for this change, including the deck framing and foundations supporting this area.
08/27/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/14/2021 NICHOLAS ROSS ZONING REVIEW Approved
09/14/2021 NROSS1 DESIGN PROFESSIONAL REVIEW Approved Design Professional Review Comments

Date: September 9, 2021

To: Nick Ross
Planning and Development Services
City of Tucson
201 N. Stone Avenue
Tucson, AZ 85701

From: R. Fe Tom, AIA, Design Professional

Project: Project Name: Benedictine Monastery Apartments
Address: 800 North Country Club Rd
Related Activity Number: # T20CM00313
DP19-0165

Re: Design Professional Review for Building Revisions


The purpose of this review is to provide a Design Professional Review for the changes being proposed the North
Building of the Benedictine Monastery for compliance with the developments standards outlined in the PAD-37
documents, approved by Mayor and Council on September 17, 2019.

Items reviewed are revised construction document plan sheets identified by Delta 32, dated 3/17/21 and a Permit
Revision Letter dated 8/2/21. Changes being proposed are the conversion of a roof to an occupiable roof deck -
located at the southwest corner of the North Building on level 2.

· Per PAD-37 Development standards: "Rooftop amenities will be allowed in the step-down areas of the
building" (part 3.C.2). The proposal conforms to allowable heights and is located at level 2 of the 3-story
building.
· Applicant shall ensure that lighting at the rooftop deck shall conform with City of Tucson Lighting code
per PAD-37 (part 3.C.11).

As the Design Professional, I recommend approval of these changes.



End of Review Comments







Richard Fe Tom, AIA
COT Design Professional

Final Status

Task End Date Reviewer's Name Type of Review Description