Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T20CM00313
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/03/2020 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | See notes for activity number T20CM00312 |
| 02/11/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T20CM00313 1. Sheet G002; Building Heights: A note indicates a horizontal assembly is provided at Level 2 per 510.2. Please add to that note that this condition is typical for all portions of the Sorth building. 2. Sheet G003; Floor Plans: Please indicate the means of egress and the exit access travel distances on the plans per the IBC Section 107.2.3, and verify the maximum distance indicated on Sheet G002 (195') is the worst case. 3. Sheet G401; Enlarged Pool Area: Is the pool, and all pool related structures, part of a separate permit? It was not included in the OK to Submit for the North Building, the South Building, or the Parking Structure. 4. Sheet G403; East Walkway Ramada: Is the ramada (2/G402) part of a separate permit? It was not included in the OK to Submit for the North or South Buildings. 5. Sheets S4, S5, and S6: Which ramada do these drawings reference? Please indicate a reference on these drawings. 6. Sheet A-S303.4; Framing Plan: Framing Plan: The Plan Title indicates 4th Floor Framing. Is this the Roof Framing Plan? Please verify. 7. Sheet A-S304.5; Framing Plan: The Plan Title indicates 5th Floor Framing. Is this the Roof Framing Plan? Please verify. 8. Sheets A-A111.1, A-A112.1, etc.: Several sheets are not sealed, signed, and dated by the registered design professional per the IBC Section 107.1. Please provide. 9. Sheet A-A116; Roof Plan: Please add a Key Plan to this sheet. 10. Sheets A-A131, A-A132, etc.; Reflected Ceiling Plans: Please add a Key Plan to these sheets. 11. Sheets A-A154, A-A155, etc.; Slab Plans: Please add a Key Plan to these sheets. 12. Sheet A-A501; Wall Type: Please indicate a U.L. Listing Number on Wall Types D1, D2, and D3. 13. Sheet A-A501; Wall Type B4: The one hour fire resistance rating provides a U.L. Listing Number, but the Wall Title indicates a two hour wall. Please verify. 14. General: Please provide dimensioned details for grab bars in restrooms/showers/tubs per the ICC/ANSI Chapter 6. 15. General: Please provide U.L. Listing Numbers for all rated slabs as required. 16. General: Are there any Special Inspections required for Site Preparation, Excavation, etc., that should be included on the Special Inspection Certificate? Please verify and add as required. 17. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 02/19/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/20/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The mechanical plan for unit 2B shows a dryer vent with a total equivalent length that is greater than 65-feet. Will a power ventilator be employed? Reference: Sections 504.8.4.1 and 504.8.4.3, IMC 2018. 2. Show how the dryer installations comply with Section 504.6, IMC 2018. 3. Provide mechanical ventilation for the residential areas of the building. Reference: Section R403.6, IECC 2018. 4. Provide calculations for the building envelope to demonstrate compliance with the energy code; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. As a minimum, the information shall include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Use the commercial section of the 2018 IECC for the common areas of the building and the residential section of the 2018 IECC for the residential areas. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2018. |
| 02/20/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide roof drainage calculations and plans for the roof located at column OO-5. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1108, IPC 2018. 2. Plumbing general note #6 calls for all sewer piping to run at 1/8" per 12" slope unless noted otherwise. Horizontal sewer pipes less than 3" require a minimum slope of ΒΌ" per 12". |
| 02/25/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet A-E200. Please apply the Keynote #2 on the site plan in the location it references. 2. Ref; Dwelling Units. (a) Include AFCI protection in Dwelling Unit Kitchens as required per NEC art 210.12A. (b) Verify that the luminaires over the showers or Bathtubs are rated for wet locations. NEC 410.10 3. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for exterior lighting. 4. Provide compliance with the 2018 IECC. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 02/25/2020 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | FROM: Samuel Rogers PDSD Zoning Review Section PROJECT: T20CM00313 Benedictine Monastery Commercial Building Plan (1st Review) 800 N Country Club Rd. TRANSMITTAL DATE: 2/25/20 DUE DATE: 2/25/20 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has reviewed the building plans for compliance with the Development Package DP19-0165. The plans appear to match the building heights, footprint, square footage, and locations on the Development Package. All other commercial reviewers must approve the plans before zoning can approve. If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or at Samuel.Rogers@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 03/02/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | 1) Once all oustanding commercial reviews are complete Engineering will conduct a final review of the building plans for consistency against the approved Development Package 2) Please update the plan set to include the approved version of the Development Package 3) Ensure that all roof drains scupper under pedestrian circulation areas |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/07/2020 | KROBLES1 | OUT TO CUSTOMER | Completed |