Permit Number: T20CM00308
Parcel: 124110540

Address:
1739 E MILES ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM

Permit Number - T20CM00308
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2020 ANDREW CONNOR NPPO REVIEW Passed
01/17/2020 TOM WEIDEMAN ENGINEERING REVIEW Completed
01/17/2020 TWEIDEM1 BUILDING-RESIDENTIAL REVIEW Reqs Change DUPLICATE PLAN SHEETS INCLUDED IN PLAN SET. PROVIDE ONE SINGLE SET FOR REVIEW.

TOM
01/21/2020 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM00308 - SFR use
Ground Mounted Solar Panel Structure (1st Review)
1739 E. Miles Street - R-2 Zoning

TRANSMITTAL DATE: January 21, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Per the approved building plans (on Micro film at PDSD - film # 9-70-06) the square footage of the living areas of the duplex is 1,390 SF.

Per UDC Art. 6 section 6.6.3.D, an accessory structure may not exceed 50% the GFA of the principal structure. The proposed freestanding ground mounted solar structure is 740 SF. The solar structure is greater than 50% the size of the principal structure.

The options are;
a. reduce the size of the solar structure to less than 50% of 1390 SF,
b. attach the solar structure to the principal structure with a minimum roof attachment that is five in width and supports a 20 LB. live load (cannot be a trellis),
c. or apply for a Board of Adjustment variance to exceed the 50% SF.


02. COMMENT: On sheet 4, label the overall and the midpoint height of the solar structure.


03. COMMENT: Resubmit the plans for review and include a response memo detailing how the zoning comments were or will be addressed.



If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Plans and response memo

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2020 TWEIDEM1 APPROVAL SHELF Completed
01/21/2020 TWEIDEM1 OUT TO CUSTOMER Completed
01/21/2020 TWEIDEM1 REJECT SHELF Completed