Permit Number: T20CM00307
Parcel: 10123516A

Address:
3738 W RIVER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00307
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2020 MROSS2 FIRE REVIEW Approved
02/18/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. The SHELVING & ANCHOR LAYOUT plan on S1 shows electrical receptacles at the counter locations. If new electric power circuits are being installed provide the circuiting designation and conductor sizes to new receptacles. NEC 110.2.
02/18/2020 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Passed
02/18/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The installation high storage racks must not obscure or block posted EXIT signage. Show the location of all EXIT signs and install directional signage where needed. IBC 1013.1.
2. Sheet A0.4 has a plan view and cross sections of a TRUCK WELL SECTIONS. If the truck wells are not part of the plan nor included in the permit, then please remove non-applicable sheets and/or details from the permit scope of plans. IBC 107.2.1.

Please provide written responses to plan review comments.
02/18/2020 RMCCOY1 WATER REVIEW Passed
02/18/2020 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2020 JWILLIA2 OUT TO CUSTOMER Completed