Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM00307
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2020 | MROSS2 | FIRE | REVIEW | Approved | |
| 02/18/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. The installation high storage racks must not obscure or block posted EXIT signage. Show the location of all EXIT signs and install directional signage where needed. IBC 1013.1. 2. Sheet A0.4 has a plan view and cross sections of a TRUCK WELL SECTIONS. If the truck wells are not part of the plan nor included in the permit, then please remove non-applicable sheets and/or details from the permit scope of plans. IBC 107.2.1. Please provide written responses to plan review comments. |
| 02/18/2020 | RMCCOY1 | WATER | REVIEW | Passed | |
| 02/18/2020 | RMCCOY1 | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/18/2020 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The SHELVING & ANCHOR LAYOUT plan on S1 shows electrical receptacles at the counter locations. If new electric power circuits are being installed provide the circuiting designation and conductor sizes to new receptacles. NEC 110.2. |
| 02/18/2020 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/26/2020 | JWILLIA2 | OUT TO CUSTOMER | Completed |