Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM00287
Parcel: 13705494B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00287
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2020 MARTIN BROWN FIRE REVIEW Approved
02/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a reduced pressure principle backflow prevention assembly for protection of the water supply to the mister pump. Locate the backflow assembly in an accessible location per the manufacturer's instructions. Show the size, route, and termination of the relief piping from the backflow assembly. Reference: Sections 608.14.2, 608.15, and 68.17.6, IPC 2018. (For revision delta-12 on sheet P2.1 only)
02/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/04/2020 ROBERT SHERRY WATER REVIEW Completed
02/12/2020 DJELLEN1 ZONING REVIEW Reqs Change FROM: David Jellen
PDSD Zoning Review Section

PROJECT: T20CM00287 - Remodel of Patio and Canopy (Commercial)
Building Plan Review (1st Review) Chik-fil-A / Related to DP19-0280
1188 W. Irvington Rd / PAD-29

TRANSMITTAL DATE: February 12, 2020

DUE DATE: February 24, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with the unapproved development package DP19-0280. While the building plans are consistent with the unapproved DP as it relates to the zoning review purview of the building footprint, building height, square footage, site conditions etc., zoning cannot approve the building plans until the DP has been approved and PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the approved DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Jellen at (520) 837-4082 or by email David.Jellen@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or Steve.Shields@tucsonaz.gov
02/12/2020 DJELLEN1 ENGINEERING REVIEW Reqs Change Engineering cannot approve the building plans until DP19-0280 has been approved.
02/20/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. The electrical sheets have letters and numbers contained in the notes and tables section that did not reproduce properly. Provide sheets where all letters and numbers are legible. IBC 107.2.1
02/20/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The City of Tucson has adopted the 2018 edition of the International Codes including the Building Code and the 2017 National Electric Code. Please correct the Building Data text box and verify compliance with the adopted codes. IBC 107.2.1.
2. Indicate the building code occupancy classification and construction type for the new canopy. Specify the canopy area and maximum allowable area. IBC 107.2.1.
3. Indicate the building code occupancy classification for the building. IBC 302.1.
4. Provide an architectural site plan of the entire lot and show the location of the canopy and distance from the existing building(s) and property boundaries. IBC 107.2.1.
5. Provide a scope of work in the architectural plans which includes the canopy if this is included in the construction plans. IBC 107.2.1.
6. Provide structural details and calculations for the light poles. IBC 107.2.1.
7. The structural calculations are referencing the 2012 International Building Code. The City of Tucson has adopted the 2018 International Building Code. Please recalculate and reference design to the 2018 IBC.
IBC 107.2.1.
8. Correct all structural notes in the canopy construction plans to the 2018 International Building Code. IBC 107.2.1. and verify compliance. IBC 107.2.1.
9. Provide general structural notes for the canopy structural plans; indicate design loads, referenced codes, specifications and required special inspections. IBC 1603.1.
10. On structural sheet AB1 of 2 the occupancy category for the canopy is listed as M occupancy which is not the correct occupancy category for vehicle related use. IBC 302.1.
11. Indicate the height of the canopy measured from finish surface to the bottom of the mist fans or the lowest projection from the roof. IBC 107.2.1.
12. The NOTE on sheet T-1.1 is referencing sheet A1.0 for ACCESSIBILITY NOTES, LIFE SAFETY NOTES and CODE SUMMARIES; which is missing from the construction documents. Provide this referenced sheet with all listed information. IBC 107.2.1.
13. Provide an occupant load for the indoor and outdoor seating; submit minimum plumbing fixture calculations for the total occupant load. IBC TABLE 2902.1.
14. Identify not less than (1) accessible dining surface in the new outdoor dining area. IBC 1109.11

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2020 LBOWERS1 OUT TO CUSTOMER Completed
04/24/2020 LBOWERS1 REJECT SHELF Completed