Permit Number: T20CM00261
Parcel: 140260090

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00261
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2020 IMONSHI1 ZONING REVIEW Approved
01/14/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide listing information for the tortilla machine and its installation.
2. Provide a thimble for the roof penetration.
3. Provide specifications for the flue assembly
01/14/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The vent for the grease interceptor may not run horizontally prior to rising 6" above the flood rim of the grease interceptor.
01/14/2020 IMONSHI1 ENGINEERING REVIEW Passed
01/14/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Passed
01/14/2020 ROBERT SHERRY WATER REVIEW Completed
01/14/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/14/2020 MARTIN BROWN FIRE REVIEW Approved
01/21/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Completed