Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM00261
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/14/2020 | IMONSHI1 | ZONING | REVIEW | Approved | |
01/14/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide listing information for the tortilla machine and its installation. 2. Provide a thimble for the roof penetration. 3. Provide specifications for the flue assembly |
01/14/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The vent for the grease interceptor may not run horizontally prior to rising 6" above the flood rim of the grease interceptor. |
01/14/2020 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
01/14/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Passed | |
01/14/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/14/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/14/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/21/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Completed |