Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM00205
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2020 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 01/10/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating/cooling load calculations for the new A/C unit. 2. Revise the ventilation calculations using the occupant density shown in Table 403.3.1.1, IMC 2018. |
| 01/10/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1 Provide compliance with the 2018 IECC for the lighting. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 01/10/2020 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
| 01/10/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/10/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/10/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify (i.e.show) the installation of the hot water recirculation system. 2. All lavatories located in public restrooms require the installation of metering faucets. 3. Correct detail B4 to locate the shutoff valve upstream of the dirt leg. |
| 01/10/2020 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 01/10/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |