Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T20CM00182
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2020 | AMARTIN1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/27/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/30/2020 | STANTEC | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a design for the mounting shelves for the booster pumps along with structural calculations to show that the units are safely supported from the building structure. Reference: Section 301.2, IPC 2018. 2. Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour (0.031 GPM/SF). Reference: Sections 1101.7, 1106, and 1108, IPC 2018. |
| 01/30/2020 | STANTEC | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018. 2. The mechanical COMcheck indicates that the "Additional Efficiency Package Options" (C406, IECC 2018) is to be accomplished using reduced interior lighting power. Show how this is to be accomplished. Reference: Section C401.2, IECC 2018. |
| 01/30/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/31/2020 | STANTEC | ENGINEERING | REVIEW | Approved | |
| 02/05/2020 | IMONSHI1 | ZONING | REVIEW | Reqs Change | FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: T19CM00182 - New Building Building Plan Review (1st Review) / Relate to DP14-0248 10185 E Old Vail / C-1 Zoning TRANSMITTAL DATE: February 5th, 2020 DUE DATE: February 14th, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building plans are consistent with the approved DP as it relates to the zoning review purview of the Building footprint, Height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans. 2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. 3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 02/18/2020 | STANTEC | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 02/18/2020 | STANTEC | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/19/2020 | PMARTIN1 | OUT TO CUSTOMER | Completed |