Permit Number: T20CM00074
Parcel: 11202033P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM00074
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The shower pan detail does not comply with the rquirements of Section 421.5, IPC 2018. [Initial comment: Provide details showing how the floor of the shower on the first floor is to be constructed in accordance with the requirements of 421.5, IPC 2018.]
02/05/2020 MARTIN BROWN FIRE REVIEW Approved
02/06/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed