Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
01/14/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
01/14/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/14/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Closet installations of domestic clothes dryers (exhausting less than 200 CFM) require an opening in the dryer enclosure of at least 100 square inches. Reference: Section 504.6, IMC 2018. [Initial comment: Show how the dryer installation in each apartment complies with Section 504.6, IMC 2018.]
01/16/2020 DJELLEN1 ZONING REVIEW Approved Comment #3 has not been addressed. Provide previous plans showing the unit as being 2 separate units or provide parking calculations showing required number of spaces are met with the new additional unit.
01/28/2020 AMARTIN1 FIRE REVIEW Needs Review